Product Description: The YQGM100 series gas transmission module is based on various gas sensors and is compatible with detection principles such as electrochemical, infrared, catalytic combustion, zirconia, and fluorescence methods. It utilizes a high-precision computing circuit and a 16-bit imported AD converter to collect sensor signals. After undergoing intelligent software algorithms and standard gas calibration, the sensor signals are converted into standard signals such as Modbus and 4-20mA for output. Internally, it integrates a microprocessor intelligent algorithm, high-precision operational amplifier circuit, constant potential circuit, filtering, and temperature compensation circuits. The module boasts a comprehensive set of output interfaces, supporting RS485, 4-20mA, I2C, and wireless output. It is compatible with sensors of multiple principles and supports detection of extremely low concentrations. It requires no calibration and can be used directly, greatly meeting users’ needs for low-cost, embedded applications.

Threshold check / alarm setpoint? Quick links to engineer tools:
🧪 Concentration Converter →
⚙️ GB Alarm Calculator →
Product Overview
Application Scenarios
Core Features: Complete output interfaces, compatibility with multi-principle sensors, 16-bit AD acquisition, intelligent software algorithms, direct use without calibration, support for extremely low concentration detection, segmented LCD display, audible and visual alarms, and relay output
Product Features:
* Fixed/portable pump-aspirated explosion-proof electrochemical sensor for catalytic combustion detection
☆ The output interfaces are comprehensive, including RS485 (standard Modbus), 4-20mA, I2C, etc., with optional wireless outputs (GPRS, RF, WIFI, Zigbee, etc.)
☆ Compatible with various sensors such as electrochemical, infrared, pump-aspirated, catalytic combustion, zirconia, and fluorescence methods
☆ High-precision amplification and intelligent software algorithms ensure precise measurement results with good consistency
☆Calibration-free, ready-to-use, convenient and quick
☆ Supports detection of extremely low concentrations
☆ The segmented display screen shows information such as gas name, concentration, unit, and range, making real-time values and built-in parameters clear at a glance
☆ Supports setting gas names and full-scale ranges through software or buttons, compatible with ppm, %LEL, %VOL units, with menu options for calibration, and includes a data recovery function
☆Audible and visual alarms, with relay output capable of interfacing with peripheral devices
Product Specifications
1. Performance
Detected Gases: CH4, CO, O3, HF, CO2, etc. (For specific gases, please refer to the selection table or consult us.)
Sensor Principle: electrochemical, catalytic combustion, infrared, zirconia, fluorescence, etc
Accuracy: ±3%
Repeatability: ±3%
Measurement Range: Determined by the gas being detected (please consult for specific ranges)
Resolution: Determined based on the gas being detected and the measurement range (supporting detection of extremely low concentrations)
Response time: Determined based on the gas being detected (please consult)
2. Electrical characteristics
Input Voltage: DC24V (12~30V)
Power Consumption: <1W (toxic gas); <2W (catalytic combustion, infrared); <3W (other)
Output mode: RS485 (standard Modbus), 4~20mA, wireless output (GPRS, RF, WIFI, Zigbee, etc.); other output signals can be customized
Display: Segmented LCD display: gas name, concentration, unit, range, etc
Relay capacity: 0.5A@24VDC
Alarm mode: audible and visual alarm
Parameter Settings: The software or buttons are used to set the gas name and full-scale range; compatible units include ppm, %LEL, and %VOL; menu options allow for calibration; and it features a data recovery function
3. Structural Characteristics
Sensor Housing: Material: aluminum alloy; Shape: cylindrical; M20×1.5 (connected to the housing); M40×1.5 (threaded for pipeline connection); Height: 57mm
Outline dimensions: Please refer to the product size diagram or consult the manufacturer for details
Protection level: Please consult the manufacturer
Overall weight: Please consult the manufacturer
Installation method: cup thread connection, supports pipeline installation
4. Certification and Implementation Standards
Compliance Standards: For specific certifications and compliance standards, please consult the manufacturer
5. Operating Environment
Temperature Range: -40~70℃ (catalytic combustion); -20~50℃ (electrochemical sensor)
Humidity Range: 0~95%RH (non-condensing)